Our DIL Switch Addressed (DSA) Context Plus temperature detectors have a low air flow resistance case made of self-extinguishing white polycarbonate. The devices monitor temperature by using a single thermistor network which provides a voltage output proportional to the external air temperature.
The response to heat increases of the standard temperature detector enables the detector to be utilised as an EN54–5:2000 A2S heat detector, which is equivalent to an EN54–5:1984 Grade 2 detector. A high temperature detector, which has similar characteristics at 25°C but reaches a 55 count at 90°C, is available for use in normal ambient temperatures of up to 55°C. This detector meets the requirements for a CS detector in EN54–5:2000.
The address of DSA Context Plus temperature detectors is set using the DIL switch located on the underside of the device. All segments are set to 0 (ON) or 1 (OFF), using a small screwdriver or similar tool. The address should be written on the label and the rear of the detector sealed.
Specifications